Friday, December 12, 2014

Engr. Aneel Kumar

SPECIAL CONSIDERATIONS AFFECTING PUMPED STORAGE PLANTS

A pumped storage unit is one in which the turbine and generator are operated in the reverse direction to pump water from the lower reservoir to the upper reservoir. The generator becomes a motor, drawing its energy from the power system, and supplies mechanical power to the turbine which acts as a pump.

The motor is started with the wicket gates closed and the draft tube water depressed with compressed air. The motor is accelerated in the pump direction and when at full speed and connected to the power system, the depression air is expelled, the pump is primed, and the wicket gates are opened to commence pumping action.

PUMP MOTOR STARTING

Various methods are utilized to accelerate the generator/motor in the pump direction during starting. These include:

1. Full voltage, across the line starting. Used primarily on smaller units, the unit breaker is closed and the unit is started as an induction generator. Excitation is applied near rated speed and machine reverts to synchronous motor operation.

2. Reduced voltage, across the line starting. A circuit breaker connects the unit to a starting bus tapped from the unit step-up transformer at one third to one half rated voltages. Excitation is applied near rated speed and the unit is connected to the system by means of the generator circuit breaker. Alternative methods include use of a series reactor during starting and energization of partial circuits on multiple circuit machines.

3. Pony motor starting. A variable speed wound-rotor motor attached to the AC station service and coupled to the motor/generator shaft is used to accelerate the machine to synchronous speed.

4. Synchronous starting. A smaller generator, isolated from the power system, is used to start the motor by connecting the two in parallel on a starting bus, applying excitation to both units, and opening the wicket gates on the smaller generator. When the units reach synchronous speed, the motor unit is disconnected from the starting bus and connected to the power system.

5. Semi-synchronous (reduced frequency, reduced voltage) starting. An isolated generator is accelerated to about 80% rated speed and paralleled with the motor unit by means of a starting bus. Excitation is applied to the generating unit and the motor unit starts as an induction motor. When the speed of the two units is approximately equal, excitation is applied to the motor unit, bringing it into synchronism with the generating unit. The generating unit is then used to accelerate both units to rated speed and the motor unit is connected to the power system.

6. Static starting. A static converter/inverter connected to the AC station service is used to provide variable frequency power to accelerate the motor unit. Excitation is applied to the motor unit at the beginning of the start sequence and the unit is connected to the power system when it reaches synchronous speed. The static starting system can be used for dynamic braking of the motor unit after disconnection from the power system, thus extending the life of the unit’s mechanical brakes.

PHASE REVERSING OF THE GENERATOR/MOTOR

It is necessary to reverse the direction of rotation of the generator/motor by interchanging any two of the three phases. This is achieved with multi-pole motor operated switches or with circuit breakers.

DRAFT TUBE WATER DEPRESSION

Water depression systems using compressed air are provided to lower the level of the draft tube water below the runner to minimize the power required to accelerate the motor unit during the transition to pumping mode. Water depression systems are also used during motoring operation of a conventional hydroelectric unit while in synchronous condenser mode. Synchronous condenser operation is used to provide voltage support for the power system and to provide spinning reserve for rapid loading response when required by the power system.

Engr. Aneel Kumar -

Subscribe to this Blog via Email :