n'/> Skip to main content

Factors Affecting Corona in Overhead Transmission Lines

Factors Affecting Corona in Overhead Transmission Lines

Author: Engr. Aneel Kumar

Factors affecting corona discharge in transmission lines infographic
Figure 1: Infographic illustrating the factors influencing corona discharge in transmission lines.

Introduction

The corona effect in overhead transmission lines is a phenomenon that occurs when the electric field intensity around conductors exceeds a critical value, causing ionization of the surrounding air. This ionization produces bluish light, hissing sound, power loss, and ozone gas. While corona may seem undesirable, it also has a few advantages such as reducing overvoltages by absorbing surges.

Corona directly impacts power system efficiency, transmission losses, equipment life, and design cost. Therefore, engineers must understand the factors affecting corona in detail to ensure efficient and reliable design of high-voltage transmission systems.

1. Conductor Size (Diameter)

The diameter of the conductor plays a crucial role in corona formation. A larger conductor size results in lower surface electric field intensity, which increases the corona inception voltage and decreases the chances of corona discharge. This is why bundled conductors are extensively used in EHV (Extra High Voltage) and UHV (Ultra High Voltage) systems.

For example, a 400 kV line with a single conductor may produce heavy corona, but the same line using bundled conductors will experience significantly less corona discharge. This reduces corona loss, audible noise, and radio interference.

2. Spacing Between Conductors

The spacing between conductors directly influences the electric field intensity. If conductors are placed close to each other, the field intensity increases and corona is more likely. By increasing conductor spacing, the disruptive critical voltage can be raised, thus reducing corona.

However, excessive spacing is not desirable because it increases tower size, cost, and right-of-way requirements. Therefore, an optimal balance between mechanical design and electrical performance must be achieved.

3. System Voltage

Corona effect is directly proportional to system voltage. At low voltages (below 30 kV), corona is negligible. However, at 220 kV, 400 kV, and higher transmission lines, corona becomes a major consideration in design. Engineers design lines such that the operating voltage is kept well below the corona inception voltage under fair weather conditions.

If the operating voltage is too close to the critical disruptive voltage, corona becomes continuous, leading to severe power losses and interference.

4. Atmospheric Conditions

The atmospheric conditions significantly affect corona performance. In rain, fog, snow, and dust, the conductor surface becomes irregular due to moisture or particles, which reduces the corona inception voltage. This results in a higher intensity of corona discharge.

In fair weather, corona is less severe and often negligible for properly designed systems. Thus, engineers design lines considering worst-case weather scenarios.

5. Conductor Surface Condition

The surface condition of conductors is another critical factor. Smooth, polished conductors maintain uniform electric field distribution, while rough or stranded conductors intensify the electric field at certain points, leading to early corona onset.

Corrosion, dust deposition, and aging of conductors worsen this effect. This is why transmission companies prefer conductors with protective coatings and periodic maintenance to keep surfaces clean.

6. Line Frequency

The frequency of the supply system also impacts corona. Corona loss increases with frequency because ionized particles oscillate more rapidly. Since most power systems operate at 50 Hz or 60 Hz, this factor remains constant; however, HVDC systems are immune to corona loss due to frequency effects.

7. Air Density and Pressure

The air density factor (δ) depends on altitude, temperature, and pressure. At higher altitudes, the air is thinner and offers less insulation strength, reducing the corona inception voltage. This makes corona more prominent in hilly or mountainous regions compared to coastal or plain regions.

Engineers apply correction factors while designing transmission lines for different altitudes to account for this variation.

Comparative Table: Factors vs. Effect on Corona

Factor Influence on Corona
Conductor SizeLarger diameter reduces corona effect by lowering surface electric field intensity.
Conductor SpacingIncreased spacing raises corona inception voltage and reduces corona discharge.
System VoltageHigher operating voltage increases corona intensity and losses.
Atmospheric ConditionsRain, fog, snow, and dust lower inception voltage, increasing corona.
Conductor Surface ConditionRough, dirty, or corroded surfaces intensify electric fields and promote corona.
Line FrequencyCorona loss increases with frequency; HVDC is immune to this effect.
Air DensityLow air density at high altitudes reduces inception voltage, increasing corona.

Advantages of Corona

  • Reduces the severity of voltage surges and transients.
  • Acts as a natural regulator by limiting voltage peaks.
  • Provides a visible and audible warning of over-voltage conditions.

Disadvantages of Corona

  • Causes corona loss, reducing transmission efficiency.
  • Produces radio interference and audible noise.
  • Generates ozone and nitrous oxides, which deteriorate insulation.
  • Leads to power quality issues in nearby communication systems.
  • Reduce transmission line efficiency.
  • Leads to audible hissing and visual glow - undesirable in populated areas.

Conclusion

The corona effect is an inevitable phenomenon in high-voltage transmission lines, but its severity can be minimized through careful design, choice of conductor, optimal spacing, weather considerations, and maintenance. While it has certain advantages such as surge absorption, its disadvantages like power loss and interference outweigh the benefits in most cases.

By understanding the factors affecting corona, engineers can design transmission systems that balance reliability, efficiency, and cost-effectiveness, ensuring long-term stability of the power grid.

Popular posts from this blog

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

Advantages of Per Unit System in Power System Analysis | Electrical Engineering

  Advantages of Per Unit System in Power System Analysis In electrical power engineering, the per unit (p.u.) system is one of the most widely used techniques for analyzing and modeling power systems. It is a method of expressing electrical quantities — such as voltage, current, power, and impedance — as fractions of chosen base values rather than their actual numerical magnitudes. This normalization technique provides a universal language for system calculations, minimizing errors, simplifying transformer modeling, and enabling consistency across multiple voltage levels. Because of these benefits, the per unit system is essential in fault analysis, load flow studies, transformer testing, and short-circuit calculations . ⚡ What is the Per Unit System? The per unit system is defined as: Q u a n t i t y ( p u ) = A c t u a l   V a l u e B a s e   V a l u e Quantity_{(pu)} = \dfrac{Actual \ Value}{Base \ Value} Q u an t i t y ( p u ) ​ = B a se   ...

PHASOR DIAGRAM OF A TWO AXIS SALIENT POLE GENERATOR

Following phasor is phsor diagram of a two-axis salient pole generator . The following points apply to the drawing of phasor diagrams of generators and motors:- • The terminal voltage V is the reference phasor and is drawn horizontally. • The emf E lies along the pole axis of the rotor. • The current in the stator can be resolved into two components, its direct component along the ‘direct or d-axis’ and its quadrature component along the ‘quadrature or q-axis’. The emf E leads the voltage V in an anti-clockwise direction when the machine is a generator. Each reactance and resistance in the machine has a volt drop associated with it due to the stator current flowing through it. Consider a generator. The following currents and voltages can be shown in a phasor diagram for both the steady and the dynamic states. E                      the emf produced by the field current If . V    ...

DISTRIBUTION STATCOM D-STATCOM

The D-STATCOM is basically one of the custom power devices. It is nothing but a STATCOM but used at the Distribution level. The D-STATCOM is a voltage or current source inverter based custom power device connected in shunt with the power system. It is connected near the load at the distribution systems. The key component of the D-STATCOM is a power VSC that is based on high power electronics technologies. Basically, the D-STATCOM system is comprised of three main parts: a VSC, a set of coupling reactors and a controller. The basic principle of a D-STATCOM installed in a power system is the generation of a controllable ac voltage source by a voltage source converter (VSC) connected to a dc capacitor (energy storage device). The ac voltage source, in general, appears behind a transformer leakage reactance. The active and reactive power transfer between the power system and the D-STATCOM is caused by the voltage difference across this reactance. The D-STATCOM is connected in shunt w...

ADVANTAGES AND DISADVANTAGES OF CORONA EFFECT IN TRANSMISSION LINES | ELECTRICAL ENGINEERING GUIDE

Advantages and Disadvantages of Corona Effect in Power Systems In high-voltage overhead transmission lines , the corona effect plays a critical role in system performance. Corona occurs when the air around a conductor becomes ionized due to high electric stress. While often seen as a drawback because of power losses and interference , it also provides certain engineering benefits . This article explains the advantages and disadvantages of corona effect in detail, with examples relevant to modern electrical power systems. ✅ Advantages of Corona Effect Increase in Virtual Conductor Diameter Due to corona formation, the surrounding air becomes partially conductive, increasing the virtual diameter of the conductor. This reduces electrostatic stress between conductors and minimizes insulation breakdown risks. Related Reading: Electrostatic Fields in High Voltage Engineering Reduction of Transient Surges Corona acts like a natural cushion for sudden ...

DC GENERATORS

Principle: An electrical generator is a machine which converts mechanical energy into electrical energy. The energy conversion is based on the principle of the production of dynamically induced emf, where a conductor cuts magnetic flux, dynamically induced emf is produced in it according to Faraday’s Laws of electromagnetic Induction. This emf causes a current to flow if the conductor circuit is closed. Hence, two basic essential parts of an electrical generator are (i) a magnetic field and (ii) a conductor or conductors which can so move as to cut the flux. The following figure shows a single-turn rectangular copper coil rotating about its own axis in a magnetic field provided by either permanent magnets or electromagnets. The two ends of the coil are joined to two slip-rings ‘a’ and ‘b’ which are insulated from each other and from the central shaft. Two collecting brushes (of carbon or copper) press against the slip-rings. Their function is to collect the current induced in the coi...

Operation of Thyristor Controlled Series Capacitor (TCSC): Mechanism and Working Principles

Introduction In modern power systems, maintaining voltage stability and optimizing power transmission is crucial. One of the most effective FACTS (Flexible AC Transmission System) controllers for this purpose is the Thyristor Controlled Series Capacitor (TCSC) . TCSC dynamically adjusts line impedance , allowing for enhanced power flow, transient stability improvement, and subsynchronous resonance (SSR) mitigation . Unlike conventional fixed series capacitors, TCSC uses thyristor-controlled switching to regulate the compensation level in real-time, ensuring grid reliability and efficiency . In this article, we will explore: ✅ The working principle and internal structure of TCSC ✅ Modes of operation and impedance control mechanisms ✅ How TCSC enhances power system efficiency and stability Understanding the Thyristor Controlled Series Capacitor (TCSC) What is a TCSC? A Thyristor Controlled Series Capacitor (TCSC) is a power electronic-based controller used in transmission systems to ...