n'/> Skip to main content

NAVIGATION AIDS

Navigation aids consist of the following equipment:

1. Flashing marker lights.
2. Fog horns.
3. Platform nameplates.
4. Aircraft hazard lights.
5. Helideck landing facilities.
6. Radio communications and beacons.
7. Radar.
8. Echo-sounding and sonar.

1) FLASHING MARKER LIGHTS

A typical requirement is that recommended by the British Department of Trade document ‘Standard Making Schedule for Offshore Installations’,

1. White and red lights flashing the Morse letters ‘U’ every 15 seconds as follows:

Eclipse 1.00 s
Flash 1.00 s
Eclipse 1.00 s
Flash 3.00 s
Eclipse 8.00 s
Total Period 15.00 s

2. Fog signals sounding the ‘U’ every 30 seconds as follows:

Blast 0.75 s
Silent 1.00 s
Blast 0.75 s
Silent 1.00 s
Blast 2.50 s
Silent 24.00 s
Total Period 30.00 s

3. Illuminated identification panels.
4. Navigation buoys.

2) WHITE AND RED FLASHING LIGHTS

The ‘normal’ range and ‘apparent intensity’ of these flashing lights should be in accordance with the local requirements, e.g. for UK waters, IALA publication ‘Recommendations for the Notation of Luminous Intensity and Range of Lights’.

a) MAIN LIGHTS

The main white lights should have a ‘nominal’ range of 15 miles and be visible in every direction of approach; there should normally be a minimum of two and a maximum of four main white lights.

b) SUBSIDIARY LIGHTS

Subsidiary red lights of 3 miles ‘nominal’ range should be positioned to mark the horizontal extremities of the structure, in positions not occupied by white lights, to indicate any irregular projections of the complex.

c) SECONDARY LIGHTS

Secondary white lights of 10 miles ‘nominal’ range and visible in every direction of approach should automatically come into operation in the event of failure of the 15 mile main white lights; these are normally mounted in similar location to the main white lights.

d) OPERATION AND CONTROL OF LIGHTING SYSTEMS

Navigation lighting systems can be fitted with a device to automatically switch on 15 minutes before sunset until sunrise or whenever the visibility is less than 2 sea miles. There can also be a manual override device to enable the navigation aids to be switched on during unusual conditions or for maintenance and testing etc.

Failure of any of the navigation lights can be indicated in the central control room and in the radio room.

In the event of failure of the main white lights control equipment, control should automatically be transferred to the secondary system, which would cause the secondary and the main lights to flash in synchronism, and generate an alarm in the central control room and the radio room.

All subsidiary lights should operate in synchronism.

The secondary and subsidiary lights can be equipped with an automatic lamp changer or multiple filament bulbs. This provides a minimum of one standby lamp or filament which will be automatically activated in the event of a filament failure. Filament failure should produce an alarm in the central control room and the radio room until a defective bulb is replaced.

On long narrow structures or structures linked by bridges where lights may otherwise be several hundred metres apart, intermediary 3 mile red lights should be mounted in positions to deter vessel from colliding with the central sections of the structure of bridges.

The secondary and subsidiary lights should be capable of operating for 96 hours from a battery power source which is independent of the main supply. The equipment would normally operate on the main AC supply, with automatic switching to an alternative AC supply in the event of main supply failure, and automatic switching to battery supplies when no AC supply is available.

3) NAVIGATION BUOYS

Navigation marker buoys can be wave or solar powered or alternatively fitted with batteries. They would be retained in a position to facilitate quick manual launching, and provision should be made for ready inspection and maintenance of batteries.

4) IDENTIFICATION PANELS

The structure identification panels usually consist of black letter and figures one metre high on a yellow background with illumination or be on a retro-reflective background.

5) AIRCRAFT HAZARD LIGHTING

Hazard lighting should be provided on all projections from the structure which could present a danger to helicopters approaching the platform. Positions where it would be impractical to fit red lights due to the possibility of damage or difficulty of maintenance caused by high temperature, such as flare towers and exhaust stacks, would be flood lit from convenient locations.

In the event of main supply failure the hazard lighting would be supplied from an emergency generator or battery supply.

No form of lighting on the structure should be capable of creating a hazard to helicopters by night-blinding the pilot due to dazzle or glare.

6) HELICOPTER LANDING FACILITIES

Helideck markings and illumination should be in accordance with appropriate standards.

A high frequency radio beacon with a minimum range of 30 miles can be provided for the guidance of approaching helicopters, and VHF/AM radio would be provided for communication with pilots to comply with the appropriate standards, for the location.

The structure would also be equipped with suitable devices for ascertaining the wind speed and direction, air temperature, barometric pressure, visibility and cloud cover.

7) RADAR

Radar is not used on all offshore platforms. Its use is determined by the nature of the platform and the frequency and type of local sea traffic. When surveillance radar is installed precautions should be adopted to ensure the minimum of danger to personnel from high energy radiation and dangers associated with rotating aerial scanners, interference with electronic instruments and communication, and the elimination of ignition in hazardous atmosphere in accordance with the standards e.g. BS3192 and 4992.

All of the equipment and interconnecting cables should be located in a safe area. The transmitters and aerials should not be located near telecommunication equipment, electronic instruments and similar equipment which could suffer interference or damage due to high energy radio frequency radiation. The aerials must be positioned to prevent the creation of high energy radio frequency fields in hazardous areas where they could cause ignition.

The aerials should be installed in such a manner and location as to allow reasonable safe access for at least two people for servicing and maintenance, whilst preventing access to un-authorized personnel.

Emergency stop switches could be provided in a safe position, adjacent to the aerials, to switch off the scanners and transmitters.

8) RADIO DIRECTION-FINDER

Platforms that are permanently manned would require equipment for obtained bearings on radio navigation beacons and survival craft transmitting on international distress frequencies. If the equipment is of a type approved by the British Department of Trade (or similar national standard) in accordance with SOLAS (1974) Regulation 12, then the SOLAS requirements could also be supplemented as follows:

• The equipment should be located in the radio room.
• The aerials and feeder cables should be located in a safe area as close as possible to the radio room.
• An emergency power supply should provide a minimum of 6 hours duration, and minimum of 3 hours of this supply should be from batteries. The batteries, charger and supply cables should be in a safe area as close as possible to the radio room.

9) SONAR DEVICES

If echo-sounding equipment is required then it should be of a type approved by the Department of Trade, or similar national authority appropriate to the location, in accordance with SOLAS (1974). The installation of sonar devices should be in accordance with appropriate standards, and particular regard should be directed towards the dangers that high-powered underwater sonar transmissions may present during diving operations.

Comments

Popular posts from this blog

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

Advantages of Per Unit System in Power System Analysis | Electrical Engineering

  Advantages of Per Unit System in Power System Analysis In electrical power engineering, the per unit (p.u.) system is one of the most widely used techniques for analyzing and modeling power systems. It is a method of expressing electrical quantities — such as voltage, current, power, and impedance — as fractions of chosen base values rather than their actual numerical magnitudes. This normalization technique provides a universal language for system calculations, minimizing errors, simplifying transformer modeling, and enabling consistency across multiple voltage levels. Because of these benefits, the per unit system is essential in fault analysis, load flow studies, transformer testing, and short-circuit calculations . ⚡ What is the Per Unit System? The per unit system is defined as: Q u a n t i t y ( p u ) = A c t u a l   V a l u e B a s e   V a l u e Quantity_{(pu)} = \dfrac{Actual \ Value}{Base \ Value} Q u an t i t y ( p u ) ​ = B a se   ...

PHASOR DIAGRAM OF A TWO AXIS SALIENT POLE GENERATOR

Following phasor is phsor diagram of a two-axis salient pole generator . The following points apply to the drawing of phasor diagrams of generators and motors:- • The terminal voltage V is the reference phasor and is drawn horizontally. • The emf E lies along the pole axis of the rotor. • The current in the stator can be resolved into two components, its direct component along the ‘direct or d-axis’ and its quadrature component along the ‘quadrature or q-axis’. The emf E leads the voltage V in an anti-clockwise direction when the machine is a generator. Each reactance and resistance in the machine has a volt drop associated with it due to the stator current flowing through it. Consider a generator. The following currents and voltages can be shown in a phasor diagram for both the steady and the dynamic states. E                      the emf produced by the field current If . V    ...

DISTRIBUTION STATCOM D-STATCOM

The D-STATCOM is basically one of the custom power devices. It is nothing but a STATCOM but used at the Distribution level. The D-STATCOM is a voltage or current source inverter based custom power device connected in shunt with the power system. It is connected near the load at the distribution systems. The key component of the D-STATCOM is a power VSC that is based on high power electronics technologies. Basically, the D-STATCOM system is comprised of three main parts: a VSC, a set of coupling reactors and a controller. The basic principle of a D-STATCOM installed in a power system is the generation of a controllable ac voltage source by a voltage source converter (VSC) connected to a dc capacitor (energy storage device). The ac voltage source, in general, appears behind a transformer leakage reactance. The active and reactive power transfer between the power system and the D-STATCOM is caused by the voltage difference across this reactance. The D-STATCOM is connected in shunt w...

ADVANTAGES AND DISADVANTAGES OF CORONA EFFECT IN TRANSMISSION LINES | ELECTRICAL ENGINEERING GUIDE

Advantages and Disadvantages of Corona Effect in Power Systems In high-voltage overhead transmission lines , the corona effect plays a critical role in system performance. Corona occurs when the air around a conductor becomes ionized due to high electric stress. While often seen as a drawback because of power losses and interference , it also provides certain engineering benefits . This article explains the advantages and disadvantages of corona effect in detail, with examples relevant to modern electrical power systems. ✅ Advantages of Corona Effect Increase in Virtual Conductor Diameter Due to corona formation, the surrounding air becomes partially conductive, increasing the virtual diameter of the conductor. This reduces electrostatic stress between conductors and minimizes insulation breakdown risks. Related Reading: Electrostatic Fields in High Voltage Engineering Reduction of Transient Surges Corona acts like a natural cushion for sudden ...

DC GENERATORS

Principle: An electrical generator is a machine which converts mechanical energy into electrical energy. The energy conversion is based on the principle of the production of dynamically induced emf, where a conductor cuts magnetic flux, dynamically induced emf is produced in it according to Faraday’s Laws of electromagnetic Induction. This emf causes a current to flow if the conductor circuit is closed. Hence, two basic essential parts of an electrical generator are (i) a magnetic field and (ii) a conductor or conductors which can so move as to cut the flux. The following figure shows a single-turn rectangular copper coil rotating about its own axis in a magnetic field provided by either permanent magnets or electromagnets. The two ends of the coil are joined to two slip-rings ‘a’ and ‘b’ which are insulated from each other and from the central shaft. Two collecting brushes (of carbon or copper) press against the slip-rings. Their function is to collect the current induced in the coi...

Operation of Thyristor Controlled Series Capacitor (TCSC): Mechanism and Working Principles

Introduction In modern power systems, maintaining voltage stability and optimizing power transmission is crucial. One of the most effective FACTS (Flexible AC Transmission System) controllers for this purpose is the Thyristor Controlled Series Capacitor (TCSC) . TCSC dynamically adjusts line impedance , allowing for enhanced power flow, transient stability improvement, and subsynchronous resonance (SSR) mitigation . Unlike conventional fixed series capacitors, TCSC uses thyristor-controlled switching to regulate the compensation level in real-time, ensuring grid reliability and efficiency . In this article, we will explore: ✅ The working principle and internal structure of TCSC ✅ Modes of operation and impedance control mechanisms ✅ How TCSC enhances power system efficiency and stability Understanding the Thyristor Controlled Series Capacitor (TCSC) What is a TCSC? A Thyristor Controlled Series Capacitor (TCSC) is a power electronic-based controller used in transmission systems to ...