Friday, December 12, 2014

Engr. Aneel Kumar

THERMAL PLANT AUXILIARY SYSTEM

SELECTION OF AUXILIARY SYSTEM VOLTAGES

The most common plant auxiliary system voltages are 13,800 V, 6900 V, 4160 V, 2400 V, and 480 V. The highest voltage is determined by the largest motor. If motors of 4000 hp or larger are required, one should consider using 13,800 V. If the largest motor required is less than 4000 hp, then 4160 V should be satisfactory.

AUXILIARY SYSTEM LOADS

Auxiliary load consists of motors and transformers. Transformers supply lower level buses which supply smaller motors and transformers which supply lower voltage buses. Generation plants built before 1950 may have an auxiliary generator that is connected to the main generator shaft. The auxiliary generator will supply plant loads when the plant is up and running.

AUXILIARY SYSTEM POWER SOURCES

The power sources for a generating plant consist of one or more off-site sources and one or more onsite sources. The on-site sources are the generator and, in some cases, a black start diesel generator or a gas turbine generator which may be used as a peaker.

AUXILIARY SYSTEM VOLTAGE REGULATION REQUIREMENTS

Most plants will not require voltage regulation. A load flow study will indicate if voltage regulation is required. Transformers with tap changers, static VAR compensators, or induction regulators may be used to keep plant bus voltages within acceptable limits. Switched capacitor banks and overexcited synchronous motors may also be used to regulate bus voltage.

Engr. Aneel Kumar -

Subscribe to this Blog via Email :