REQUIREMENTS OF EQUIPMENTS DESIGN AND CONSTRUCTION

Oil industry equipment tends to be more robust than normal industrial equipment due to the often harsh and hostile environments in which it is expected to function without trouble for long periods of time. The indirect cost of equipment failures and outages is high and reliability is of paramount importance.

An essential requirement is the definition of the degree of protection of the enclosure for the environment, which may be either outdoor or indoor, and hazardous or non-hazardous. The international standards most often used are IEC60529 and NEMA-ICS1-110 for the degree of protection against liquids and particles. These references are applied for the hazardous area protection.

Wound components such as motor and transformer windings need to have their insulation specified to withstand the surface temperature of the copper conductors. IEC60085 and ANSI/NEMA describe the different classes of insulation that are normally available. Where IEC60085 or ANSI/NEMA is the reference, the two most common are Class B and Class F. These state the maximum temperature rise in degrees Celsius above the conductor temperature when the temperature of the cooling medium for the equipment is no greater than 40◦C.

For most equipment ratings used in the oil industry the temperature rise limits are 80◦C for Class B and 100◦C for Class F (Class H allows 125◦C). It is common practice to specify Class F insulating materials but to restrict the actual temperature rise to that of Class B. These stem from the recommendation in IEC60085 that for ratings equal and above 5000 kVA or if the iron core length is equal and above one metre, that this combination of classes should be used.

The owner may have particular requirements for the materials to be used for insulation and their impregnation. This may be due to their experience with marine and highly humid environments.

Other aspects that should be included are protective devices, measurement detectors, terminal blocks, segregation of circuits and terminals, voltage surge suppression, skid construction, floor frames, lifting eyes, jacking points, earthing bosses, indicating devices, control switches, automatic voltage regulators, exciters, detachable panels and doors, forced cooling, shaft bearings and seals, lubrication systems, anti-condensation heaters, noise levels, labelling and nameplates, painting etc. Some of these may be efficiently included in the data sheet.

Comments

Popular posts from this blog

ADVANTAGES AND DISADVANTAGES OF CORONA

Corona has many advantages and disadvantages. In the correct design of a high voltage overhead line, a balance should be struck between the advantages and disadvantages. ADVANTAGES (i) Due to corona formation, the air surrounding the conductor becomes conducting and hence virtual diameter of the conductor is increased. The increased diameter reduces the electrostatic stresses between the conductors. (ii) Corona reduces the effects of transients produced by surges. DIS-ADVANTAGES (i) Corona is accompanied by a loss of energy. This affects the transmission efficiency of the line. (ii) Ozone is produced by corona and may cause corrosion of the conductor due to chemical action. (iii) The current drawn by the line due to corona is non-sinusoidal and hence non-sinusoidal voltage drop occurs in the line. This may cause inductive interference with neighboring communication lines.

ADVANTAGES OF PER UNIT SYSTEM

PER UNIT SYSTEM The per-unit system expressed the voltages, currents, powers, impedances, and other electrical quantities basis by the equation: Quantity per unit (pu) = Actual value/ Base value of quantity ADVANTAGES OF PER UNIT SYSTEM While performing calculations, referring quantities from one side of the transformer to the other side serious errors may be committed. This can be avoided by using per unit system. Voltages, currents and impedances expressed in per unit do not change when they are referred from one side of transformer to the other side. This is a great advantage. Per unit impedances of electrical equipment of similar type usually lie within a narrow range, when the equipment ratings are used as base values. Transformer connections do not affect the per unit values. Manufacturers usually specify the impedances of machines and transformers in per unit or percent of name plate ratings. Transformers can be replaced by their equivalent series impedances. ...

ABSOLUTE AND SECONDARY INSTRUMENTS

The various electrical instruments may, in a very broad sense, be divided into (i) Absolute Instruments (ii) Secondary Instruments. Absolute Instruments are those which give the value of the quantity to be measured, in terms of the constants of the instrument and their deflection only. No previous calibration or comparison is necessary in their case. The example of such an instrument is tangent galvanometer, which gives the value of current, in terms of the tangent of deflection produced by the current, the radius and number of turns of wire used and the horizontal component of earth’s field.  Secondary Instruments  are those, in which the value of electrical quantity to be measured can be determined from the deflection of the instruments, only when they have been pre-calibrated by comparison with an absolute instrument. Without calibration, the deflection of such instruments is meaningless. It is the secondary instruments, which are most generally used in ev...