INFLUENCE OF SHORT INTERRUPTIONS ON EQUIPMENT

During a short interruption the voltage is zero; thus, there is no supply of power at all to the equipment. The temporary consequences are that there is no light, which motors slow down, that screens turn blank, etc. All this only lasts for a few seconds, but the consequences can last much longer: disruption of production processes, loss of contents of computer memory, evacuation of buildings due to fire alarms going off, and sometimes damage when the voltage comes back (uncontrolled starting).

For most sensitive equipment, there is no strict border between a voltage sag and an interruption: an interruption can be seen as a severe sag, i.e. one with zero remaining voltage.

INDUCTION MOTORS

The effect of a zero voltage on an induction motor is simple: the motor slows down. The mechanical time constant of an induction motor plus its load is in the range of 1 to 10 seconds. With dead times of several seconds, the motor has not yet come to a standstill but is likely to have slowed down significantly. This reduction in speed of the motors might disrupt the industrial process so much that the process control trips it.

The motor can re-accelerate when the voltage comes back, if the system is strong enough. For public distribution systems re-acceleration is seldom a problem.

Also the setting of the under voltage protection should be such that it does not trip before the voltage comes back. This calls for a coordination between the under voltage setting of the motor protection and the reclosure interval setting on the utility feeder.

Induction motors fed via contactors are disconnected automatically as the contactor drops out. Without countermeasures this would always lead to loss of the load. In some industrial processes the induction motors are automatically reconnected when the voltage comes back: either instantaneously or staged (the most important motors first, the rest later).

SYNCHRONOUS MOTORS

Synchronous motors can normally not restart on full load. They are therefore equipped with under voltage protection to prevent stalling when the voltage comes back. For synchronous motors the delay time of the under voltage protection should be less than the reclosing interval. Especially for very fast reclosure this can be a problem. We see here a situation where an interruption causes a more serious threat to the synchronous motors the faster the voltage comes back. With most other load the situation is the other way around: the shorter the interruption, the less severe it is to the load.

ADJUSTABLE SPEED DRIVES

Adjustable-speed drives are very sensitive to short interruptions, and to voltage sags. They normally trip well within I second, sometimes even within one cycle; thus even the shortest interruption will cause a loss of the load. Some of the more modern drives are able to automatically reconnect the moment the voltage comes back. But being disconnected from the supply for several seconds will often have disrupted the process behind the drive so much that reconnection does not make much sense anymore.

ELECTRONIC EQUIPMENT

Without countermeasures electronics devices will trip well within the reclosing interval. This leads to the infamous "blinking-clock syndrome": clocks of video recorders, microwave ovens, and electronic alarms start blinking when the supply is interrupted; and they keep on blinking until manually reset. An easy solution is to install a small rechargeable battery inside of the equipment, to power the internal memory during the interruption.

Computers and process control equipment have basically the same problem. But they require more than a simple battery. An uninterruptible power supply (UPS) is a much-used solution.

Comments

Popular posts from this blog

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

Advantages of Per Unit System in Power System Analysis | Electrical Engineering

  Advantages of Per Unit System in Power System Analysis In electrical power engineering, the per unit (p.u.) system is one of the most widely used techniques for analyzing and modeling power systems. It is a method of expressing electrical quantities — such as voltage, current, power, and impedance — as fractions of chosen base values rather than their actual numerical magnitudes. This normalization technique provides a universal language for system calculations, minimizing errors, simplifying transformer modeling, and enabling consistency across multiple voltage levels. Because of these benefits, the per unit system is essential in fault analysis, load flow studies, transformer testing, and short-circuit calculations . ⚡ What is the Per Unit System? The per unit system is defined as: Q u a n t i t y ( p u ) = A c t u a l   V a l u e B a s e   V a l u e Quantity_{(pu)} = \dfrac{Actual \ Value}{Base \ Value} Q u an t i t y ( p u ) ​ = B a se   ...

PHASOR DIAGRAM OF A TWO AXIS SALIENT POLE GENERATOR

Following phasor is phsor diagram of a two-axis salient pole generator . The following points apply to the drawing of phasor diagrams of generators and motors:- • The terminal voltage V is the reference phasor and is drawn horizontally. • The emf E lies along the pole axis of the rotor. • The current in the stator can be resolved into two components, its direct component along the ‘direct or d-axis’ and its quadrature component along the ‘quadrature or q-axis’. The emf E leads the voltage V in an anti-clockwise direction when the machine is a generator. Each reactance and resistance in the machine has a volt drop associated with it due to the stator current flowing through it. Consider a generator. The following currents and voltages can be shown in a phasor diagram for both the steady and the dynamic states. E                      the emf produced by the field current If . V    ...

DISTRIBUTION STATCOM D-STATCOM

The D-STATCOM is basically one of the custom power devices. It is nothing but a STATCOM but used at the Distribution level. The D-STATCOM is a voltage or current source inverter based custom power device connected in shunt with the power system. It is connected near the load at the distribution systems. The key component of the D-STATCOM is a power VSC that is based on high power electronics technologies. Basically, the D-STATCOM system is comprised of three main parts: a VSC, a set of coupling reactors and a controller. The basic principle of a D-STATCOM installed in a power system is the generation of a controllable ac voltage source by a voltage source converter (VSC) connected to a dc capacitor (energy storage device). The ac voltage source, in general, appears behind a transformer leakage reactance. The active and reactive power transfer between the power system and the D-STATCOM is caused by the voltage difference across this reactance. The D-STATCOM is connected in shunt w...

ADVANTAGES AND DISADVANTAGES OF CORONA EFFECT IN TRANSMISSION LINES | ELECTRICAL ENGINEERING GUIDE

Advantages and Disadvantages of Corona Effect in Power Systems In high-voltage overhead transmission lines , the corona effect plays a critical role in system performance. Corona occurs when the air around a conductor becomes ionized due to high electric stress. While often seen as a drawback because of power losses and interference , it also provides certain engineering benefits . This article explains the advantages and disadvantages of corona effect in detail, with examples relevant to modern electrical power systems. ✅ Advantages of Corona Effect Increase in Virtual Conductor Diameter Due to corona formation, the surrounding air becomes partially conductive, increasing the virtual diameter of the conductor. This reduces electrostatic stress between conductors and minimizes insulation breakdown risks. Related Reading: Electrostatic Fields in High Voltage Engineering Reduction of Transient Surges Corona acts like a natural cushion for sudden ...

DC GENERATORS

Principle: An electrical generator is a machine which converts mechanical energy into electrical energy. The energy conversion is based on the principle of the production of dynamically induced emf, where a conductor cuts magnetic flux, dynamically induced emf is produced in it according to Faraday’s Laws of electromagnetic Induction. This emf causes a current to flow if the conductor circuit is closed. Hence, two basic essential parts of an electrical generator are (i) a magnetic field and (ii) a conductor or conductors which can so move as to cut the flux. The following figure shows a single-turn rectangular copper coil rotating about its own axis in a magnetic field provided by either permanent magnets or electromagnets. The two ends of the coil are joined to two slip-rings ‘a’ and ‘b’ which are insulated from each other and from the central shaft. Two collecting brushes (of carbon or copper) press against the slip-rings. Their function is to collect the current induced in the coi...

Operation of Thyristor Controlled Series Capacitor (TCSC): Mechanism and Working Principles

Introduction In modern power systems, maintaining voltage stability and optimizing power transmission is crucial. One of the most effective FACTS (Flexible AC Transmission System) controllers for this purpose is the Thyristor Controlled Series Capacitor (TCSC) . TCSC dynamically adjusts line impedance , allowing for enhanced power flow, transient stability improvement, and subsynchronous resonance (SSR) mitigation . Unlike conventional fixed series capacitors, TCSC uses thyristor-controlled switching to regulate the compensation level in real-time, ensuring grid reliability and efficiency . In this article, we will explore: ✅ The working principle and internal structure of TCSC ✅ Modes of operation and impedance control mechanisms ✅ How TCSC enhances power system efficiency and stability Understanding the Thyristor Controlled Series Capacitor (TCSC) What is a TCSC? A Thyristor Controlled Series Capacitor (TCSC) is a power electronic-based controller used in transmission systems to ...