PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems

Author: Engr. Aneel Kumar

Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability.


Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary, Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch.

Related: Power System Stability — causes & mitigation

Primary, Secondary and Tertiary Frequency Control in Power System

Overview of primary, secondary and tertiary frequency control in power systems.

⚡ Primary Frequency Control (Droop Control)

Primary control is a fast, local response implemented by generator governors (droop control). It reacts automatically within seconds to frequency deviations by changing turbine/generator power output proportionally to frequency error. Primary action arrests the frequency fall/rise and stabilizes the system at a new quasi-steady value.

Related: The per-unit system — basics and utility

Typical primary response time is 0–30 seconds. Primary control works off the machines’ kinetic energy and governor droop settings; it does not restore frequency to nominal — that is the role of secondary control.

Related: Power system stability concepts & inertia

Advantages of Primary Control

  • Very fast, automatic local action to arrest frequency deviation.
  • No central communication required — resilient and robust.
  • Immediate support across the grid through many generators sharing the burden.

Disadvantages of Primary Control

  • Leaves frequency at a quasi-steady offset (droop causes steady error).
  • Unequal sharing if generator droops are not coordinated.
  • Relies on stored kinetic energy — limited duration and magnitude.
Dynamic and quasi-steady-state frequency deviation during primary control

Figure 1: Dynamic (Δfdyn) and quasi-steady (Δf) frequency deviation.

🔁 Secondary Frequency Control (AGC)

Secondary control is centralized Automatic Generation Control (AGC). It uses a central regulator to change generator setpoints and restore system frequency to nominal while correcting scheduled tie-line power exchanges between control areas. Secondary action typically begins to be effective after about 30 seconds and completes within minutes (often < 15 min).

Related: Power system protection & operational coordination

Advantages of Secondary Control

  • Restores frequency to nominal and corrects tie-line power flows.
  • Re-allocates generation set-points to release primary reserves.
  • Enables coordinated operation across the control area/region.

Disadvantages of Secondary Control

  • Slower than primary — takes seconds to minutes to act.
  • Requires reliable communications and centralized control systems.
  • Needs accurate measurement of tie-line power and frequency for correct operation.
Generator contribution to primary control based on droop

Figure 2: How generators with different droops contribute to primary control.

🛠️ Tertiary Frequency Control (Dispatch & Reserve Restoration)

Tertiary control is manual or automated dispatch-level action that restores secondary reserves and optimizes generation costs after disturbances. It reallocates generation set-points, starts/stops peaking units, dispatches hydro or storage resources, or modifies interchange schedules.

Advantages of Tertiary Control

  • Restores and re-allocates reserves for sustained operations.
  • Optimizes generation economically (dispatch & unit commitment).
  • Enables strategic use of storage, pumped hydro and market resources.

Disadvantages of Tertiary Control

  • Slow — not suitable for arresting immediate frequency excursions.
  • Often requires market/dispatch coordination and operator decisions.
  • Effectiveness depends on available reserves and start-up times of units.

🔍 Quick Comparison: Primary vs Secondary vs Tertiary

Feature Primary Secondary (AGC) Tertiary
Response time Seconds (0–30 s) 30 s – 15 min 15 min – hours
Main goal Arrest frequency deviation Restore nominal frequency & tie-line flows Restore reserves & economic dispatch
Control type Local / decentralized (governor) Centralized (AGC) Manual or automated dispatch
Requires communications? No Yes (measurements & telemetry) Yes (market/dispatch systems)
Restores frequency to nominal? No (leaves offset) Yes Yes — and restores reserves

⚠️ Emergency Measures & Summary

If frequency excursions exceed permissible limits, emergency actions include load shedding (under-frequency tripping) and generator disconnection (over-frequency). Effective frequency control (primary + secondary + tertiary) reduces the chance of blackouts and equipment damage by ensuring fast arrest, full restoration and economic recovery.

Timing of primary, secondary and tertiary frequency control ranges

Figure 3: Timing of primary, secondary and tertiary control ranges.

Comments

Unknown said…
when it is suitable to apply whether primary frequency control or secondary frequency control or tertiary frequency control in power system according to the percentage load disturbance
Unknown said…
yes you are right sir. its very useful article.

Popular posts from this blog

Advantages of Per Unit System in Power System Analysis | Electrical Engineering

  Advantages of Per Unit System in Power System Analysis In electrical power engineering, the per unit (p.u.) system is one of the most widely used techniques for analyzing and modeling power systems. It is a method of expressing electrical quantities — such as voltage, current, power, and impedance — as fractions of chosen base values rather than their actual numerical magnitudes. This normalization technique provides a universal language for system calculations, minimizing errors, simplifying transformer modeling, and enabling consistency across multiple voltage levels. Because of these benefits, the per unit system is essential in fault analysis, load flow studies, transformer testing, and short-circuit calculations . ⚡ What is the Per Unit System? The per unit system is defined as: Q u a n t i t y ( p u ) = A c t u a l   V a l u e B a s e   V a l u e Quantity_{(pu)} = \dfrac{Actual \ Value}{Base \ Value} Q u an t i t y ( p u ) ​ = B a se   ...

PHASOR DIAGRAM OF A TWO AXIS SALIENT POLE GENERATOR

Following phasor is phsor diagram of a two-axis salient pole generator . The following points apply to the drawing of phasor diagrams of generators and motors:- • The terminal voltage V is the reference phasor and is drawn horizontally. • The emf E lies along the pole axis of the rotor. • The current in the stator can be resolved into two components, its direct component along the ‘direct or d-axis’ and its quadrature component along the ‘quadrature or q-axis’. The emf E leads the voltage V in an anti-clockwise direction when the machine is a generator. Each reactance and resistance in the machine has a volt drop associated with it due to the stator current flowing through it. Consider a generator. The following currents and voltages can be shown in a phasor diagram for both the steady and the dynamic states. E                      the emf produced by the field current If . V    ...

DISTRIBUTION STATCOM D-STATCOM

The D-STATCOM is basically one of the custom power devices. It is nothing but a STATCOM but used at the Distribution level. The D-STATCOM is a voltage or current source inverter based custom power device connected in shunt with the power system. It is connected near the load at the distribution systems. The key component of the D-STATCOM is a power VSC that is based on high power electronics technologies. Basically, the D-STATCOM system is comprised of three main parts: a VSC, a set of coupling reactors and a controller. The basic principle of a D-STATCOM installed in a power system is the generation of a controllable ac voltage source by a voltage source converter (VSC) connected to a dc capacitor (energy storage device). The ac voltage source, in general, appears behind a transformer leakage reactance. The active and reactive power transfer between the power system and the D-STATCOM is caused by the voltage difference across this reactance. The D-STATCOM is connected in shunt w...

ADVANTAGES AND DISADVANTAGES OF CORONA EFFECT IN TRANSMISSION LINES | ELECTRICAL ENGINEERING GUIDE

Advantages and Disadvantages of Corona Effect in Power Systems In high-voltage overhead transmission lines , the corona effect plays a critical role in system performance. Corona occurs when the air around a conductor becomes ionized due to high electric stress. While often seen as a drawback because of power losses and interference , it also provides certain engineering benefits . This article explains the advantages and disadvantages of corona effect in detail, with examples relevant to modern electrical power systems. ✅ Advantages of Corona Effect Increase in Virtual Conductor Diameter Due to corona formation, the surrounding air becomes partially conductive, increasing the virtual diameter of the conductor. This reduces electrostatic stress between conductors and minimizes insulation breakdown risks. Related Reading: Electrostatic Fields in High Voltage Engineering Reduction of Transient Surges Corona acts like a natural cushion for sudden ...

DC GENERATORS

Principle: An electrical generator is a machine which converts mechanical energy into electrical energy. The energy conversion is based on the principle of the production of dynamically induced emf, where a conductor cuts magnetic flux, dynamically induced emf is produced in it according to Faraday’s Laws of electromagnetic Induction. This emf causes a current to flow if the conductor circuit is closed. Hence, two basic essential parts of an electrical generator are (i) a magnetic field and (ii) a conductor or conductors which can so move as to cut the flux. The following figure shows a single-turn rectangular copper coil rotating about its own axis in a magnetic field provided by either permanent magnets or electromagnets. The two ends of the coil are joined to two slip-rings ‘a’ and ‘b’ which are insulated from each other and from the central shaft. Two collecting brushes (of carbon or copper) press against the slip-rings. Their function is to collect the current induced in the coi...

Operation of Thyristor Controlled Series Capacitor (TCSC): Mechanism and Working Principles

Introduction In modern power systems, maintaining voltage stability and optimizing power transmission is crucial. One of the most effective FACTS (Flexible AC Transmission System) controllers for this purpose is the Thyristor Controlled Series Capacitor (TCSC) . TCSC dynamically adjusts line impedance , allowing for enhanced power flow, transient stability improvement, and subsynchronous resonance (SSR) mitigation . Unlike conventional fixed series capacitors, TCSC uses thyristor-controlled switching to regulate the compensation level in real-time, ensuring grid reliability and efficiency . In this article, we will explore: ✅ The working principle and internal structure of TCSC ✅ Modes of operation and impedance control mechanisms ✅ How TCSC enhances power system efficiency and stability Understanding the Thyristor Controlled Series Capacitor (TCSC) What is a TCSC? A Thyristor Controlled Series Capacitor (TCSC) is a power electronic-based controller used in transmission systems to ...