n'/> Skip to main content

BEHAVIOUR OF SHUNT REACTOR DURING EXTERNAL AND INTERNAL FAULTS

Shunt reactors are connected in parallel with the rest of the power network. Shunt reactor can be treated as a device with the fixed impedance value. Therefore the individual phase current is directly proportional to the applied phase voltage (i.e. I=U/Z).

Thus during external fault condition, when the faulty phase voltage is lower than the rated voltage , the current in the faulty phase will actually reduce its value from the rated value.

Depending on the point on the voltage wave when external fault happens the reduce current might have superimposed dc component. Such behavior is verified by an ATP simulation and it is shown in Figure 17.

Figure 17: External Phase A to Ground Fault, Reactor Phase Currents
As a result, shunt reactor unbalance current will appear in the neutral point as shown in Figure 18. However, this neutral point current will typically be less than 1 pu irrespective of the location and fault resistance of the external fault.

Figure 18: External Phase A to Ground Fault, Reactor Zero-sequence Currents
Similarly during an internal fault the value of the individual phase currents and neutral point current will depend very much on the position of the internal fault. Assuming that due to the construction details, internal shunt reactor phase-to-phase faults are not very likely, only two extreme cases of internal phase to ground fault scenarios will be presented here.

In the first case the Phase A winding to ground fault, 1% from the neutral point has been simulated in ATP. As a result the phase currents on the HV side (i.e. in reactor bushings) will be practically the same as before the fault as shown in Figure 19.

Figure 19: Internal Phase A Winding to Ground Fault, Phase Currents
However phase A current at the shunt reactor star point and common neutral point current will have very big value due to so-called transformer effect. These currents can be so high to even cause CT saturation as shown in Figure 20 for the common neutral point current.

Figure 20: Internal Phase A Winding to Ground Fault, Zero-sequence Currents
This type of the internal fault shall be easily detected and cleared by the differential, restricted ground fault or neutral point ground overcurrent protection, but not by reactor HV side overcurrent or HV residual ground fault protections.

In the second case the Phase A to ground fault, just between the HV CTs and shunt reactor winding (i.e. shunt reactor bushing failure) has been investigated. In this case the currents have opposite properties. The phase A current on the HV side is very big (limited only by the power system source impedance and fault resistance), while the phase A current in reactor star point will have very small value due to a fact that phase A winding is practically short-circuited.

As a result, shunt reactor unbalance current will appear in the neutral point. However, this neutral point current will typically have a value around 1 pu (i.e. similar value as during external ground fault).

That type of the internal fault (i.e. shunt reactor bushing failure) shall be easily detected and cleared by the differential, restricted ground fault or HV side overcurrent or residual ground fault protections. Neutral point ground overcurrent protection can operate with the time delay.

For internal ground fault in some other location in-between these two positions the shunt reactor currents will have values somewhere in the range limited by this two extreme cases.

Comments

Popular posts from this blog

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

Advantages of Per Unit System in Power System Analysis | Electrical Engineering

  Advantages of Per Unit System in Power System Analysis In electrical power engineering, the per unit (p.u.) system is one of the most widely used techniques for analyzing and modeling power systems. It is a method of expressing electrical quantities — such as voltage, current, power, and impedance — as fractions of chosen base values rather than their actual numerical magnitudes. This normalization technique provides a universal language for system calculations, minimizing errors, simplifying transformer modeling, and enabling consistency across multiple voltage levels. Because of these benefits, the per unit system is essential in fault analysis, load flow studies, transformer testing, and short-circuit calculations . ⚡ What is the Per Unit System? The per unit system is defined as: Q u a n t i t y ( p u ) = A c t u a l   V a l u e B a s e   V a l u e Quantity_{(pu)} = \dfrac{Actual \ Value}{Base \ Value} Q u an t i t y ( p u ) ​ = B a se   ...

PHASOR DIAGRAM OF A TWO AXIS SALIENT POLE GENERATOR

Following phasor is phsor diagram of a two-axis salient pole generator . The following points apply to the drawing of phasor diagrams of generators and motors:- • The terminal voltage V is the reference phasor and is drawn horizontally. • The emf E lies along the pole axis of the rotor. • The current in the stator can be resolved into two components, its direct component along the ‘direct or d-axis’ and its quadrature component along the ‘quadrature or q-axis’. The emf E leads the voltage V in an anti-clockwise direction when the machine is a generator. Each reactance and resistance in the machine has a volt drop associated with it due to the stator current flowing through it. Consider a generator. The following currents and voltages can be shown in a phasor diagram for both the steady and the dynamic states. E                      the emf produced by the field current If . V    ...

DISTRIBUTION STATCOM D-STATCOM

The D-STATCOM is basically one of the custom power devices. It is nothing but a STATCOM but used at the Distribution level. The D-STATCOM is a voltage or current source inverter based custom power device connected in shunt with the power system. It is connected near the load at the distribution systems. The key component of the D-STATCOM is a power VSC that is based on high power electronics technologies. Basically, the D-STATCOM system is comprised of three main parts: a VSC, a set of coupling reactors and a controller. The basic principle of a D-STATCOM installed in a power system is the generation of a controllable ac voltage source by a voltage source converter (VSC) connected to a dc capacitor (energy storage device). The ac voltage source, in general, appears behind a transformer leakage reactance. The active and reactive power transfer between the power system and the D-STATCOM is caused by the voltage difference across this reactance. The D-STATCOM is connected in shunt w...

ADVANTAGES AND DISADVANTAGES OF CORONA EFFECT IN TRANSMISSION LINES | ELECTRICAL ENGINEERING GUIDE

Advantages and Disadvantages of Corona Effect in Power Systems In high-voltage overhead transmission lines , the corona effect plays a critical role in system performance. Corona occurs when the air around a conductor becomes ionized due to high electric stress. While often seen as a drawback because of power losses and interference , it also provides certain engineering benefits . This article explains the advantages and disadvantages of corona effect in detail, with examples relevant to modern electrical power systems. ✅ Advantages of Corona Effect Increase in Virtual Conductor Diameter Due to corona formation, the surrounding air becomes partially conductive, increasing the virtual diameter of the conductor. This reduces electrostatic stress between conductors and minimizes insulation breakdown risks. Related Reading: Electrostatic Fields in High Voltage Engineering Reduction of Transient Surges Corona acts like a natural cushion for sudden ...

DC GENERATORS

Principle: An electrical generator is a machine which converts mechanical energy into electrical energy. The energy conversion is based on the principle of the production of dynamically induced emf, where a conductor cuts magnetic flux, dynamically induced emf is produced in it according to Faraday’s Laws of electromagnetic Induction. This emf causes a current to flow if the conductor circuit is closed. Hence, two basic essential parts of an electrical generator are (i) a magnetic field and (ii) a conductor or conductors which can so move as to cut the flux. The following figure shows a single-turn rectangular copper coil rotating about its own axis in a magnetic field provided by either permanent magnets or electromagnets. The two ends of the coil are joined to two slip-rings ‘a’ and ‘b’ which are insulated from each other and from the central shaft. Two collecting brushes (of carbon or copper) press against the slip-rings. Their function is to collect the current induced in the coi...

Operation of Thyristor Controlled Series Capacitor (TCSC): Mechanism and Working Principles

Introduction In modern power systems, maintaining voltage stability and optimizing power transmission is crucial. One of the most effective FACTS (Flexible AC Transmission System) controllers for this purpose is the Thyristor Controlled Series Capacitor (TCSC) . TCSC dynamically adjusts line impedance , allowing for enhanced power flow, transient stability improvement, and subsynchronous resonance (SSR) mitigation . Unlike conventional fixed series capacitors, TCSC uses thyristor-controlled switching to regulate the compensation level in real-time, ensuring grid reliability and efficiency . In this article, we will explore: ✅ The working principle and internal structure of TCSC ✅ Modes of operation and impedance control mechanisms ✅ How TCSC enhances power system efficiency and stability Understanding the Thyristor Controlled Series Capacitor (TCSC) What is a TCSC? A Thyristor Controlled Series Capacitor (TCSC) is a power electronic-based controller used in transmission systems to ...