COOLING METHODS OF POWER TRANSFORMER

As the size and capacity of the transformer increased, the associated cooling arrangement become more powerful and sophisticated. So, by definition, the transformer cooling system is such arrangement for power transformers, which limits the generated heat into a safe value by means of proper dissipation of generated heat. Different cooling system is used for different types of transformers, and they are discussed as follows.

Generally, two types of transformers are there according to the use of insulating oil, namely Dry Type Transformers and Oil Immersed Type Transformers. In oil immersed type, the transformer core is immersed into the transformer oil. Different types of cooling are needed for these two categories. In dry type transformers, air is used as the coolant medium but in oil immersed transformer (as the size and ratings both are high), both air and transformer oil are used as the coolant medium.
Dry Type Transformers
       Oil Immersed Transformers
            Air Natural Type
  Oil Natural Air Natural type (ONAN)
            Air forced Type
  Oil Natural Air forced Type (ONAf)
  Oil forced Air forced Type (OfAf)
  Oil Directed Air forced Type (ODAf)
  Oil forced Water forced Type (OfWf)

Air Natural Type:

This cooling method is used in dry type transformer with smaller ratings. As the name implies, the natural circulation of atmospheric air is used in this technique. This type of transformers is also referred as self-cooled transformer. When the transformer is operated in full load, then the temperature of the transformer becomes greater than the ambient air temperature. So, by convection process, the light and heated air gets replaced by the heavy and comparatively cool surrounding air. In this way, the generated heat is dissipated via the natural air circulation process. But this type of cooling arrangement provides satisfactory operation for low voltage transformers only.

Air forced type:

This cooling method is also used in dry type transformer but the application is also implemented in oil immersed transformers. As the name implies, in addition with natural air circulation, cool air with high velocity is provided to the core. High speed fans are provided with the transformer, and by the rotation of this fan high velocity of air is subjected to the transformer. This additional air force ensures quicker heat dissipation of the transformers. The fans are automatically controlled, that is when the temperature of the transformer core goes beyond the safe limit than all the fans are switched ON. Air forced cooling method provides better performance than natural air cooling, but additional cost is associated for the fans.

Oil Natural Air Natural (ONAN) Cooling Of Transformer:

This cooling system is used in oil immersed type transformers. This is the simplest way of cooling of oil immersed transformers. We know that, the transformer core is immersed in transformer oil. When the transformer is heated up, then temperature of oil near to the transformer core is also raised. So, the light and heated oil flows in upward direction and comparatively cool and heavy oil takes the vacuum places by natural convection process. And the heated oil releases its temperature into the atmosphere. In this way, a natural oil circulation cycle is generated and this cycle continues until the transformer temperature is tapped into a safe limit. In this method, the surface area of the oil tank is usually larger, as more surface area provides more quick heat dissipation process. But to provide more surface areas, several hollows tubular plates are attached with the transformer and they are termed as radiator. When the hot oils are circulating through the radiators, they get more surface area so the cooling rate is much higher. Also the light and heated air gets replaced by the heavy and comparatively cool surrounding air by natural process. In this way, the generated heat is dissipated via the natural air circulation process as well as natural oil circulation.

Oil Natural Air forced (ONAF) Cooling of Transformer:

The word ‘forced’ signifies that, air is forcefully applied to the transformer. High speed fans are provided with this type of cooling system. In larger rated oil immersed transformers, natural air and oil cooling is not sufficient. So, additional air force is applied to the radiator by means of those fans and this method provides quicker heat dissipation of the transformers as compared to natural oil and air cooling. All fans are automatically controlled, whenever the temperature of the transformer goes beyond the safe limit than all the fans are switched ON. But here the oil circulation process made by natural convection, that is no oil pumps are provided for this type of cooling. This method provides better performance than natural oil and air cooling, but there is an additional cost due to the fans.

Oil forced Air forced (OfAf) Cooling of Transformer:

Actually, for very large rated oil immersed transformers, heat generated is quite high. Therefore, some special cooling techniques are applied in order to provide sufficient heat dissipation. In Oil forced Air forced cooling system, both oil and air are circulated at high speed by some additional configuration. High speed fans are connected to provide additional air flow of high velocity and oil pumps are provided to circulate the oil at high velocity. So, hot oil is circulated inside the main transformer tank at larger velocity, so the rate of cooling is further increased. Therefore, in oil forced air forced cooling system; both the oil and air are forcefully applied to achieve more fast cooling process.

Oil Directed Air forced Cooling of Transformer:

This is the updated version of Oil forced Air forced cooling method. Here the Oil and Air both are applied forcefully, but the hot oil follows a specific route for flowing. Convection channels are made closer to the winding of the transformer and the transformer oil is passed through those channels. In this way, superior heat dissipation is occurred.

Oil forced Water forced Cooling of Transformer:

Water is far better coolant than atmospheric air. So, in this method water is used as the oil coolant instead of natural air. Here, the flow of hot oil is directed to a heat ex-changer where water shower is applied. So, here the oil is cooled at faster rate than natural air cooling.

Therefore, from the above discussion, we understood the necessity of transformer cooling and also learned about the various types of transformer cooling.

Comments

Nice post! Thanks for sharing!

Popular posts from this blog

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

Advantages of Per Unit System in Power System Analysis | Electrical Engineering

  Advantages of Per Unit System in Power System Analysis In electrical power engineering, the per unit (p.u.) system is one of the most widely used techniques for analyzing and modeling power systems. It is a method of expressing electrical quantities — such as voltage, current, power, and impedance — as fractions of chosen base values rather than their actual numerical magnitudes. This normalization technique provides a universal language for system calculations, minimizing errors, simplifying transformer modeling, and enabling consistency across multiple voltage levels. Because of these benefits, the per unit system is essential in fault analysis, load flow studies, transformer testing, and short-circuit calculations . ⚡ What is the Per Unit System? The per unit system is defined as: Q u a n t i t y ( p u ) = A c t u a l   V a l u e B a s e   V a l u e Quantity_{(pu)} = \dfrac{Actual \ Value}{Base \ Value} Q u an t i t y ( p u ) ​ = B a se   ...

PHASOR DIAGRAM OF A TWO AXIS SALIENT POLE GENERATOR

Following phasor is phsor diagram of a two-axis salient pole generator . The following points apply to the drawing of phasor diagrams of generators and motors:- • The terminal voltage V is the reference phasor and is drawn horizontally. • The emf E lies along the pole axis of the rotor. • The current in the stator can be resolved into two components, its direct component along the ‘direct or d-axis’ and its quadrature component along the ‘quadrature or q-axis’. The emf E leads the voltage V in an anti-clockwise direction when the machine is a generator. Each reactance and resistance in the machine has a volt drop associated with it due to the stator current flowing through it. Consider a generator. The following currents and voltages can be shown in a phasor diagram for both the steady and the dynamic states. E                      the emf produced by the field current If . V    ...

DISTRIBUTION STATCOM D-STATCOM

The D-STATCOM is basically one of the custom power devices. It is nothing but a STATCOM but used at the Distribution level. The D-STATCOM is a voltage or current source inverter based custom power device connected in shunt with the power system. It is connected near the load at the distribution systems. The key component of the D-STATCOM is a power VSC that is based on high power electronics technologies. Basically, the D-STATCOM system is comprised of three main parts: a VSC, a set of coupling reactors and a controller. The basic principle of a D-STATCOM installed in a power system is the generation of a controllable ac voltage source by a voltage source converter (VSC) connected to a dc capacitor (energy storage device). The ac voltage source, in general, appears behind a transformer leakage reactance. The active and reactive power transfer between the power system and the D-STATCOM is caused by the voltage difference across this reactance. The D-STATCOM is connected in shunt w...

ADVANTAGES AND DISADVANTAGES OF CORONA EFFECT IN TRANSMISSION LINES | ELECTRICAL ENGINEERING GUIDE

Advantages and Disadvantages of Corona Effect in Power Systems In high-voltage overhead transmission lines , the corona effect plays a critical role in system performance. Corona occurs when the air around a conductor becomes ionized due to high electric stress. While often seen as a drawback because of power losses and interference , it also provides certain engineering benefits . This article explains the advantages and disadvantages of corona effect in detail, with examples relevant to modern electrical power systems. ✅ Advantages of Corona Effect Increase in Virtual Conductor Diameter Due to corona formation, the surrounding air becomes partially conductive, increasing the virtual diameter of the conductor. This reduces electrostatic stress between conductors and minimizes insulation breakdown risks. Related Reading: Electrostatic Fields in High Voltage Engineering Reduction of Transient Surges Corona acts like a natural cushion for sudden ...

DC GENERATORS

Principle: An electrical generator is a machine which converts mechanical energy into electrical energy. The energy conversion is based on the principle of the production of dynamically induced emf, where a conductor cuts magnetic flux, dynamically induced emf is produced in it according to Faraday’s Laws of electromagnetic Induction. This emf causes a current to flow if the conductor circuit is closed. Hence, two basic essential parts of an electrical generator are (i) a magnetic field and (ii) a conductor or conductors which can so move as to cut the flux. The following figure shows a single-turn rectangular copper coil rotating about its own axis in a magnetic field provided by either permanent magnets or electromagnets. The two ends of the coil are joined to two slip-rings ‘a’ and ‘b’ which are insulated from each other and from the central shaft. Two collecting brushes (of carbon or copper) press against the slip-rings. Their function is to collect the current induced in the coi...

Operation of Thyristor Controlled Series Capacitor (TCSC): Mechanism and Working Principles

Introduction In modern power systems, maintaining voltage stability and optimizing power transmission is crucial. One of the most effective FACTS (Flexible AC Transmission System) controllers for this purpose is the Thyristor Controlled Series Capacitor (TCSC) . TCSC dynamically adjusts line impedance , allowing for enhanced power flow, transient stability improvement, and subsynchronous resonance (SSR) mitigation . Unlike conventional fixed series capacitors, TCSC uses thyristor-controlled switching to regulate the compensation level in real-time, ensuring grid reliability and efficiency . In this article, we will explore: ✅ The working principle and internal structure of TCSC ✅ Modes of operation and impedance control mechanisms ✅ How TCSC enhances power system efficiency and stability Understanding the Thyristor Controlled Series Capacitor (TCSC) What is a TCSC? A Thyristor Controlled Series Capacitor (TCSC) is a power electronic-based controller used in transmission systems to ...