Monday, June 09, 2014

Engr. Aneel Kumar

SHUNT REACTOR APPLICATIONS

Switching of shunt reactors (and other devices characterized as having small inductive currents such as transformer magnetizing currents, motor starting currents, etc.) can generate high phase-to-ground over-voltages as well as severe recovery voltages, especially on lower voltage equipment such as reactors applied on the tertiary of transformers. Energizing the devices seldom generates high overvoltages, but overvoltages generated during de-energizing, as a result of current chopping by the switching device when interrupting the small inductive currents, can be significant. Neglecting damping, the phase-to-ground overvoltage magnitude can be estimated by:
Where i is the magnitude of the chopped current (0 to perhaps as high as 10 A or more), L is the reactor’s inductance, and C is the capacitance of the reactor (on the order of a few thousand picofarads). When C is small, especially likely with dry-type reactors often used on transformer tertiaries, the surge impedance term can be large, and hence the overvoltage can be excessive.

To mitigate the over-voltages, surge arresters are sometimes useful, but the application of a capacitor on the terminals of the reactor (or other equipment) have a capacitance on the order of 0.25–0.5 μF is very helpful. In the equation above, note that if C is increased from pF to μF, the surge impedance term is dramatically reduced, and hence the voltage is reduced.

Engr. Aneel Kumar -

Subscribe to this Blog via Email :