FACTORS TO BE CONSIDERED AT THE DESIGN STAGE OF A POWER PLANT

The electrical engineer should take full account of the site location and environmental conditions that a gas turbine generator will need to endure. These conditions can seriously affect the electrical power output that will be achievable from the machine. The starting point when considering the possible output is the ISO rating.

This is the declared rating of the machine for the following conditions:-

• Sea level elevation.
• 150C (590F) ambient temperature.
• Basic engine, no losses for inlet or exhaust systems, no losses for gearbox and mechanical transmission.
• Clean engine, as delivered from the factory.

The gas turbine manufacturer provides a standardized mechanical output power versus ambient temperature characteristic. (Some manufacturers also give the electrical output power versus ambient temperature characteristic. Therefore care must be exercised to be sure exactly which data are to be given and used.)

The following derating factors should be used in the estimation of the continuous site rating for the complete machine:

• ISO to a higher site ambient temperature, typically 0.5 to 0.8% per ◦C.
• Altitude, usually not necessary for most oil industry plants since they are near sea level.
• Dirty engine losses and the ageing of the gas turbine, assume 5%.
• Fuel composition and heating value losses, discuss with the manufacturer.
• Silencer, filter and ducting losses, assume 2 to 5%.
• Gearbox loss, typically 1 to 2%.
• Generator electromechanical inefficiency, typically 2 to 4%.
• Auxiliary loads connected to the generator, typically 1 to 5%.

Dirty engine losses

Consideration should be given to the fact that engines become contaminated with the combustion deposits, the lubrication oil becomes less efficient, blades erode and lose their thermodynamic efficiency and air filters become less efficient due to the presence of filtered particles. These effects combine to reduce the output of the machine. A rule-of-thumb figure for derating a gas turbine for dirty engine operation is 5%. This depends upon the type of fuel, the type of engine, the environment and how long the engine operates between clean-up maintenance periods. Individual manufacturers can advise suitable data for their engines operating in particular conditions. Dirty engine conditions should be considered, otherwise embarrassment will follow later once the machine is in regular service.

Fuel composition and heating value losses

The chemical composition and quality of the fuel will to some extent influence the power output. However, it is usually the case that more or less fuel has to be supplied by the fuel control valve for a given throughput of combustion air. Hence it is usually possible to obtain the declared normal rating from the machine, but attention has to be given to the supply of the fuel. In extreme cases the profile of the fuel control valve may require modification so that adequate feedback control is maintained over the full range of power output. The appropriate derating factor is usually 100%, i.e. no derating.

Silencer, filter and ducting losses

The amount of silencing and filtering of the inlet combustion air depends upon the site environment and the operational considerations.

Site environmental conditions may be particularly bad, e.g. deserts where sand storms are frequent; offshore where rain storms are frequent and long lasting. The more filtering that is required, the more will be the pressure lost across the filters, both during clean and dirty operation. This pressure drop causes a loss of power output from the machine.

The amount of inlet and exhaust noise silencing will depend upon, the location of machine with respect to people in say offices or control rooms, how many machines will be in one group since this affects the maintenance staff and total noise level permitted by international or national standards. The effects of a silencer are similar to a filter since the silencing elements cause a pressure drop.

With offshore platforms it is not always practical to locate the main generators in a good place regarding the position and routing of the inlet and exhaust ducting. Long runs of ducting are sometimes unavoid- able. It is then necessary to allow a derating factor for the pressure drop that will occur. The manufacturer should be consulted for advice on this aspect. For a typical offshore or onshore situation with a reason- able degree of silencing a rule-of-thumb derating factor would be 98%. In a poor location assume 95%.

Comments

Popular posts from this blog

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

Advantages of Per Unit System in Power System Analysis | Electrical Engineering

  Advantages of Per Unit System in Power System Analysis In electrical power engineering, the per unit (p.u.) system is one of the most widely used techniques for analyzing and modeling power systems. It is a method of expressing electrical quantities — such as voltage, current, power, and impedance — as fractions of chosen base values rather than their actual numerical magnitudes. This normalization technique provides a universal language for system calculations, minimizing errors, simplifying transformer modeling, and enabling consistency across multiple voltage levels. Because of these benefits, the per unit system is essential in fault analysis, load flow studies, transformer testing, and short-circuit calculations . ⚡ What is the Per Unit System? The per unit system is defined as: Q u a n t i t y ( p u ) = A c t u a l   V a l u e B a s e   V a l u e Quantity_{(pu)} = \dfrac{Actual \ Value}{Base \ Value} Q u an t i t y ( p u ) ​ = B a se   ...

PHASOR DIAGRAM OF A TWO AXIS SALIENT POLE GENERATOR

Following phasor is phsor diagram of a two-axis salient pole generator . The following points apply to the drawing of phasor diagrams of generators and motors:- • The terminal voltage V is the reference phasor and is drawn horizontally. • The emf E lies along the pole axis of the rotor. • The current in the stator can be resolved into two components, its direct component along the ‘direct or d-axis’ and its quadrature component along the ‘quadrature or q-axis’. The emf E leads the voltage V in an anti-clockwise direction when the machine is a generator. Each reactance and resistance in the machine has a volt drop associated with it due to the stator current flowing through it. Consider a generator. The following currents and voltages can be shown in a phasor diagram for both the steady and the dynamic states. E                      the emf produced by the field current If . V    ...

DISTRIBUTION STATCOM D-STATCOM

The D-STATCOM is basically one of the custom power devices. It is nothing but a STATCOM but used at the Distribution level. The D-STATCOM is a voltage or current source inverter based custom power device connected in shunt with the power system. It is connected near the load at the distribution systems. The key component of the D-STATCOM is a power VSC that is based on high power electronics technologies. Basically, the D-STATCOM system is comprised of three main parts: a VSC, a set of coupling reactors and a controller. The basic principle of a D-STATCOM installed in a power system is the generation of a controllable ac voltage source by a voltage source converter (VSC) connected to a dc capacitor (energy storage device). The ac voltage source, in general, appears behind a transformer leakage reactance. The active and reactive power transfer between the power system and the D-STATCOM is caused by the voltage difference across this reactance. The D-STATCOM is connected in shunt w...

ADVANTAGES AND DISADVANTAGES OF CORONA EFFECT IN TRANSMISSION LINES | ELECTRICAL ENGINEERING GUIDE

Advantages and Disadvantages of Corona Effect in Power Systems In high-voltage overhead transmission lines , the corona effect plays a critical role in system performance. Corona occurs when the air around a conductor becomes ionized due to high electric stress. While often seen as a drawback because of power losses and interference , it also provides certain engineering benefits . This article explains the advantages and disadvantages of corona effect in detail, with examples relevant to modern electrical power systems. ✅ Advantages of Corona Effect Increase in Virtual Conductor Diameter Due to corona formation, the surrounding air becomes partially conductive, increasing the virtual diameter of the conductor. This reduces electrostatic stress between conductors and minimizes insulation breakdown risks. Related Reading: Electrostatic Fields in High Voltage Engineering Reduction of Transient Surges Corona acts like a natural cushion for sudden ...

DC GENERATORS

Principle: An electrical generator is a machine which converts mechanical energy into electrical energy. The energy conversion is based on the principle of the production of dynamically induced emf, where a conductor cuts magnetic flux, dynamically induced emf is produced in it according to Faraday’s Laws of electromagnetic Induction. This emf causes a current to flow if the conductor circuit is closed. Hence, two basic essential parts of an electrical generator are (i) a magnetic field and (ii) a conductor or conductors which can so move as to cut the flux. The following figure shows a single-turn rectangular copper coil rotating about its own axis in a magnetic field provided by either permanent magnets or electromagnets. The two ends of the coil are joined to two slip-rings ‘a’ and ‘b’ which are insulated from each other and from the central shaft. Two collecting brushes (of carbon or copper) press against the slip-rings. Their function is to collect the current induced in the coi...

Operation of Thyristor Controlled Series Capacitor (TCSC): Mechanism and Working Principles

Introduction In modern power systems, maintaining voltage stability and optimizing power transmission is crucial. One of the most effective FACTS (Flexible AC Transmission System) controllers for this purpose is the Thyristor Controlled Series Capacitor (TCSC) . TCSC dynamically adjusts line impedance , allowing for enhanced power flow, transient stability improvement, and subsynchronous resonance (SSR) mitigation . Unlike conventional fixed series capacitors, TCSC uses thyristor-controlled switching to regulate the compensation level in real-time, ensuring grid reliability and efficiency . In this article, we will explore: ✅ The working principle and internal structure of TCSC ✅ Modes of operation and impedance control mechanisms ✅ How TCSC enhances power system efficiency and stability Understanding the Thyristor Controlled Series Capacitor (TCSC) What is a TCSC? A Thyristor Controlled Series Capacitor (TCSC) is a power electronic-based controller used in transmission systems to ...