Skip to main content

Posts

DISTRIBUTION SYSTEM

That part of power system which distributes electric power for local use is known as distribution system. In general, the distribution system is the electrical system between the sub-station fed by the transmission system and the consumer’s meters. It generally consists of feeders, distributors and the service mains. Fig. 12.1 shows the single line diagram of a typical low tension distribution system. (I) FEEDERS: A feeder is a conductor which connects the sub-station (or localized generating station) to the area where power is to be distributed. Generally, no tapings are taken from the feeder so that current in it remains the same throughout. The main consideration in the design of a feeder is the current carrying capacity. (II) DISTRIBUTOR: A distributor is a conductor from which tapings are taken for supply to the consumers. In Fig. 12.1, AB, BC, CD and DA are the distributors. The current through a distributor is not constant because tapings are taken at various places along...

TYPES OF CABLE FAULTS

Cables are generally laid directly in the ground or in ducts in the underground distribution system. For this reason, there are little chances of faults in underground cables. However, if a fault does occur, it is difficult to locate and repair the fault because conductors are not visible. Nevertheless, the following are the faults most likely to occur in underground cables: (i) Open-circuit fault (ii) Short-circuit fault (iii) Earth fault. (I) OPEN-CIRCUIT FAULT: When there is a break in the conductor of a cable, it is called open circuit fault. The open-circuit fault can be checked by a megger. For this purpose, the three conductors of the 3-core cable at the far end are shorted and earthed. Then resistance between each conductor and earth is measured by a megger. The megger will indicate zero resistance in the circuit of the conductor that is not broken. However, if the conductor is broken, the megger will indicate infinite resistance in its circuit. (II) SHOR...

CONVENTIONAL SOURCES OF ELECTRICAL ENERGY

Thermal (coal, gas, nuclear) and hydro-generations are the main conventional methods of generation of Electrical Energy. These enjoy the advantages of reaching perfections in technologies for these processes. Further, single units rated at large power-outputs can be manufactured along with main components, auxiliaries and switch- gear due to vast experiences during the past century. These are efficient and economical. These suffer from the disadvantages listed below: 1. The fuels are likely to be depleted in near future, forcing us to conserve them and find alternative resources. 2. Toxic, hazardous fumes and residues pollute the environment. 3. Overall conversion efficiency is poor. 4. Generally, these are located at remote places with respect to main load centers, increasing the transmission costs and reducing the system efficiency. 5. Maintenance costs are high. Out of these, only two such types will be dealt here, which have a steam turbine working as the prime mover. While remaini...

ROLE OF INSULATORS

Insulators for an overhead power line (OHL), in many substation applications and on the overhead electrification systems of railways, must, primarily, support the conductors. Also important, as already mentioned, is the need to avoid frequent flashover events from occurring. Although the total mechanical failure of such an insulator is, fortunately, a rare event, its occurrence may be very serious. For example, should a vertical insulator of an OHL (often referred to as a suspension unit) break, then its conductor could be supported by the insulators of the neighboring support structures (often called towers) at either side. Then, it is possible that this conductor could be reenergized but with little ground clearance! The consequences of a flashover vary from being annoying to being very costly. For example, the damage resulting from the external flashover of the insulating housing of a high power circuit breaker during a synchronizing operation, when the voltage across the polluted...

TYPES OF INSULATORS

There are several types of insulators but the most commonly used are pin type, suspension type, strain insulator and shackle insulator. PIN TYPE INSULATORS The pin type insulator is secured to the cross-arm on the pole. There is a groove on the upper end of the insulator for housing the conductor. The conductor passes through this groove and is bound by the annealed wire of the same material as the conductor. Pin type insulators are used for transmission and distribution of electric power at voltages up to 33 kV. Beyond operating voltage of 33 kV, the pin type insulators become too bulky and hence uneconomical. SUSPENSION TYPE INSULATORS For high voltages (>33 kV), it is a usual practice to use suspension type insulators consist of a number of porcelain discs connected in series by metal links in the form of a string. The conductor is suspended at the bottom end of this string while the other end of the string is secured to the cross-arm of the tower. Each unit or disc is desig...

ABSOLUTE AND SECONDARY INSTRUMENTS

The various electrical instruments may, in a very broad sense, be divided into (i) Absolute Instruments (ii) Secondary Instruments. Absolute Instruments are those which give the value of the quantity to be measured, in terms of the constants of the instrument and their deflection only. No previous calibration or comparison is necessary in their case. The example of such an instrument is tangent galvanometer, which gives the value of current, in terms of the tangent of deflection produced by the current, the radius and number of turns of wire used and the horizontal component of earth’s field.  Secondary Instruments  are those, in which the value of electrical quantity to be measured can be determined from the deflection of the instruments, only when they have been pre-calibrated by comparison with an absolute instrument. Without calibration, the deflection of such instruments is meaningless. It is the secondary instruments, which are most generally used in ev...

BATTERIES FOR AIRCRAFT AND SUBMARINES

BATTERIES FOR AIRCRAFT The on-board power requirements in aircraft have undergone many changes during the last three or four decades. The jet engines of the aircraft which require starting currents of about 1000A impose a heavy burden on the batteries. However, these days this load is provided by small Turbo-generator sets and since batteries are needed only to start them, the power required is much less. These batteries possess good high-rate capabilities in order to supply emergency power for up to 1 h in the event of the generator failure. However, their main service is as a standby power for miscellaneous on-board equipment. Usually, batteries having 12 cells (of a nominal voltage of 24 V) with capacities of 18 and 34 Ah at the 10 h rate are used. In order to reduce weight, only light-weight high impact polystyrene containers and covers are used and the cells are fitted with non-spill vent-plugs to ensure complete un-spill-ability in any aircraft position during aerobatics. Simi...