The speed of a permanently split capacitor motor can be adjusted by connecting it to a variable voltage source such as an auto-transformer. The limitation of this method is that the starting torque developed is very low, especially when the motor is started on low speed. Another limitation is that speed is sensitive to voltage changes on low speed connections. Further speed varies considerably for different loading conditions of the motor.
The motor can be started in three different ways using an auto-transformer as shown in Figure 1. In Figure 1 (a) the voltage across the main winding and the auxiliary winding are varied simultaneously resulting in low starting torque for low speed operation. This shortcoming, however, can be overcome by first starting the motor on high speed and then stepping it down to low speed as shown in Figure 1 (a).
Good starting torque at all speeds can be obtained if the auxiliary winding is connected across the mains supply and voltage adjustment is provided only for the main winding as shown in Figure 1 (b).
In the third method of connections shown in Figure 1 (c), the two windings are connected to a tapped auto transformer so that any voltage change across the main winding is accompanied by an inverse change across the auxiliary winding. This method with a properly designed motor can be applied to an installation whose speed should not be sensitive to variations of normal line voltage.
Figure 1 Voltage control method for speed adjustment of
split capacitor motors
|
Figure 2 Speed control of split capacitor motor with
intermediate winding
|
Connections shown in Figure 2 (b) are used for 230 voltage motors.